Power System Analysis Lecture Notes Ppt -

| Concept | Formula | |---------|---------| | Base impedance | ( Z_base = V_base^2 / S_base ) | | Y-bus element | ( Y_ik = -y_ik ) (off-diag) | | Newton-Raphson | ( \beginbmatrix \Delta P \ \Delta Q \endbmatrix = J \beginbmatrix \Delta \delta \ \Delta |V| \endbmatrix ) | | Sym. fault current | ( I_f = V_th / (Z_th+Z_f) ) | | SLG fault | ( I_f = 3V_f / (Z_1+Z_2+Z_0) ) | | Swing equation | ( (2H/\omega_s) d^2\delta/dt^2 = P_m - P_e ) |

[ C = \frac2\pi \epsilon_0\ln(D/r) \ \textF/m ]

| Line type | R (Ω/km) | L (mH/km) | C (nF/km) | |-----------|----------|-----------|-----------| | Short (<80 km) | lumped | ignored | ignored | | Medium (80–240 km) | lumped | lumped | lumped (π model) | | Long (>240 km) | distributed parameters | | | 4. Load Flow Analysis (PPT Module 4) Goal: Determine voltage magnitude & angle at each bus for given loads/generations. power system analysis lecture notes ppt

neglected for overhead lines.

Critical clearing angle ( \delta_c ) increases with higher inertia, faster fault clearing. 8. Conclusion & Summary Tables (PPT Final Module) Key formulas card: | Concept | Formula | |---------|---------| | Base

Convert a 10% transformer reactance from 20 MVA, 132 kV to 100 MVA, 132 kV → ( Z_pu,new = 0.1 \times (1)^2 \times (100/20) = 0.5 ) pu. 3. Transmission Line Parameters (PPT Module 3) Resistance: ( R = \rho \fraclA ) (corrected for skin effect at 50/60 Hz).

[ Z_pu,new = Z_pu,old \times \left( \fracV_base,oldV_base,new \right)^2 \times \left( \fracS_base,newS_base,old \right) ] neglected for overhead lines

Fault clears at angle ( \delta_c ). System stable if area ( A_1 ) (accelerating) = area ( A_2 ) (decelerating).